D-M111
 
How to adjust push S/W (see the picture No.¨ç~¨ë)
1. The LED ¨Ø display meter input maximum value. To confirm the setting value.
  A manual working condition is obtained by pushing the button ¨ëas follow
 
  Other displays except input value return to the input max. value mode after 6 secs.
2. Operating value and operating time setting. By pressing the button ¨ê and ¨ë for
  3secs at the same time, the "setting mode" will be entered the "LED" ¨Ø flashes then press the button ¨ë to change the flashing value of the display and use the button ¨ê to increase the count of it. after setting the input value, press the button ¨ê and ¨ë for 3secs at the same time to save the value of selection. (Display will be shown as below)
 
  If manual operation is not obtained for 6 secs while the LED is flashing , the LED will be returnde to the input mode.(Maximum input value)
3. Meter Relay Operating
  -This meter is able to set the time 0 to 99 seconds. If the input value is lower
  than Low setting value or higher than High setting value, the relay contacts are operated after presetting time.
(During Presetting time the LED ¨è or ¨é flashes, then after presetting time the LED is lightened and its replay is operated)
  -When the auxiliary power is connected the initial time, Low relay will not orerate
  without an input value which is higher than the low setting value at first.(It is to preventing the operating the relay without input value at the initial)
  -For turning off low relay operating set 0 to the low setting value.
  -High setting value should be set higher than the input maximum value of meter to
  be off the high relay operating.
4. Demand Meter Operating
  -Demand of peak Value will be indicated as memory (3Digital) the max one at only
  of many peack values.
  -The rating of digital is same as analogue and full scale of is same as on analogue.
  -The peak value always turns on is the digital display, it is reset the peak value by
  pressing the button. (push S/W¨ê)
  -When auxiliary power loss occurs, the peak value will be accumulated in S-RAM.
  When auxiliary power returns, the peak value will be dispalyed in the digital display.
  -If an external reset terminal is connected on push button S/W, at in possible to
  reset on outside.
Name of
meter
Shpe of
case
Type Rating Operating
Princ.
Accur.
(%)
Freq. Burden Aux
Power
Demand Meter &
Meter Relay Meter
Rectangular
(110¡¿110§®)
D-M111 1A, 5A ¡¾1.5% 50Hz
or
60Hz
1VA AC220
or
AC110