To deal with current exceeding 5A, use a 5A(1A) meter in combination with a C.T.
A.C ammeter is used with a current transfomer externally mounted, and it is noted that
  primary current of a current transformer and a full scale of the meter are identical when used.
If the circuit voltage exceeds 500V even when the current is less than 5A use
  a 5A(1A) meter in combination with a C.T to ensure insulation.
The scale range of ammeter for motor circuit is extended up to 150%~500% of rated
  current, so that these meters ard proteced from the impact of the starting current and ensured of long life.
Am expanded scale has the normal maximum reading(upper limit of effective
  measurement range) at the app. 65% point on the scale, and the rest of it (65%~100%) is devoted to extension reading. (tolerance extension area :¡¾5%)
For higher ranges 30A, use external shunt with a 50mV(60mV) instrument.
When D.C ammeter is used with a shunt, it is noted that a full scale and a terminal
  voltage(50mV, 60mV) of the ammeter are same as the rated primary current and
secondary voltage of the shunt respectively.
Use any leadwire of which resistance is less then 0.05§Ù in total.
  If the shunt lead resistance is indefinite, the meters may be set up with a available
resistor(V.R) for sensitivity adjustment.
The shunt should be connected to the negative side linc.
 
 