 |
Operating
voltage range is ¡¾10% of rated voltage. |
 |
For other voltage and/or current ratings
higher then listed on the specification,
use |
|
external
C.T and/or external P.T with a 110V/5A instrument,
when ordering, specofy
the full scale value desired, P.T ratio
and C.T ratio. |
 |
Rating voltage
of 3phase 3wire is at phase voltage..(/¡î3) |
 |
The full scale
of varmeter is generally 1/2, 1/3, or 1/4
of load capaciry. |
 |
When using P.T and C.T, Calibrating vars
will be as follows |
|
Calibrating var =  |
|
Namely 1 ) The standard calibration var
of the meter for single phase 2wire |
|
: 300Var (0.3Kvar)
|
|
2 ) Single phase
3wire : 500Var (0.5Kvar) |
|
3 ) 3phase 3wire
: 500Var (0.5Kvar) |
|
4 ) 3pgase 4wire
: 833Var (0.833Kvar) |
|
The other 1) In case of 22900V |
|
- Calibrating
var of 3phase 3wire : 480 Var |
|
- Calibrating
var of 3phase 4wire : 833 Var |
|
The other 2 ) In case of 380V |
|
-
3phase 3wire use to potential transformer
ratio 380V/110V : 579Var |
|
- not use to
potential transformer : 2.0Kvar |
|
- 3phase 4wire
use to potential transformer ratio V
/ V
: 1.0Kvar |
|
The other 3) In case of V |
|
- no use to
potential transformer at 3phase 4wire :
1.0kvar |
 |
The standard scale is LGA. |
 |
The varmeter with "0" point
at center is recomended, if it is used instead
of a power |
|
factor meter.
In case of using the varmeter as a power
factor meterm it is recommended,
to use a left side and of "0"
point at the center as Lead-O-LAG. |
¡Ø The instrument of D-V¡à¡à¡àT
Type is self contained with the Transducer
Box. |